Internal contaminants and decay of concentration
The impacts of the global pandemic are numerous however one in particular has been a better understanding of the importance of good ventilation in buildings. Specifically the World Health Organisation published information about the airborne transmission of COVID-19, which further emphasises the importance of good, effective ventilation.
One of the specific terms relating to air contamination and the impacts of air replacement can be referred to as decay of concentration, also referred to as half-life which describes the impact air change rates have in the dilution or decay of a contaminant contained with in air.
The decay of the concentration can be expressed by the equation:
- C = Cmax . (e -t/)
- C = [Cmax, 0] as t = [0, ∞)
Where:
- t is the time from the start of the rise or decay (s)
- τ is known as the “half-life” or air change (s)
- C is the concentration at time t (ppm)
- Cmax is the maximum concentration during rise or decay (ppm)
- τ is calculated by:
= V/Q
Where:
- V is the volume of the room (m3)
- Q is the ventilation rate (m3/s)
The initial concentration before any decay, is the maximum concentration described as Cmax. When t=τ (half-life or 1 air change), then the concentration in the room has reduced to 0.37Cmax. and when t=3τ, then the concentration C= 0.05.Cmax. This means that after 3 half-lives, the concentration in the room has been reduced by 95%.
Therefore in practice, 3 τ is considered to be the time to achieve steady state conditions, for a rise, or the time to clear the room, for a decay.
We do have to take into account the fact that the air supplied must be fresh, i.e. not recirculated and that the ventilation must be effective; fresh air must not be short circuited into the extract and it must reach everywhere in the room, to avoid areas of high contaminant concentration (stagnation).
The mechanical air change rate provided by the ventilation system is not often the same as the effective air change rate. The concept of a “mixing factor, k” can be used to describe the quality or effectiveness of the mixing process in a space. Mathematically, Q'=kQ where k = 1 for ideal mixing and k = 0.5 for poor mixing. The effect on decay levels is shown in the following equation:
Where:
- τ’ is the room’s “half-life” (s)
- V is the room’s volume (m3)
- Q is the mechanical, theoretical ventilation rate (m3/s)
- Q’ is the effective ventilation rate (m3/s)
Substituting the k value into the decay equation, the following expression is obtained:
C = Cmax . (e -t.k/)
For example, for a k factor of 0.6, when t=τ(half-life), then the concentration in the room has reduced to 0.55 Cmax, instead of the original 0.37Cmaxand when t=3τ, then the concentration is still 0.17.Cmax, compared to 0.05 for k=1.
This means that it will take longer to purge the contaminant from the room i.e. If the ACR of an isolation room is 10 ACH, for a k value of 0.6, the effective ventilation rate would be 6 ACH.
BSRIA has studied several hospital isolation rooms, with dedicated ventilation. The k factor in those rooms, which were considered well-mixed, was k= 0.8, calculated using gas tracer methodologies.
This is based on an article published on the BSRIA website as "New World Health Organisation information emphasises effective ventilation in buildings" dated June 2020.
[edit] Related articles on Designing Buildings
- Air change rates.
- Air filtration and clean Indoor air quality standards.
- Air tightness in buildings.
- At a glance - Indoor air quality.
- BSRIA articles on Designing Buildings Wiki.
- Ensuring good indoor air quality in buildings.
- HVAC balancing.
- HVAC industry defines post COVID-19 changes.
- Indoor air quality.
- Indoor air velocity.
- Let us evolve our buildings from being passive structures to interactive and reactive systems.
- Mechanical ventilation's role in improving indoor air quality.
- Timber and healthy interiors.
- Ventilation.
- Ventilation and control of COVID-19 transmission.
Featured articles and news
A change to adoptive architecture
Effects of global weather warming on architectural detailing, material choice and human interaction.
How big is the problem and what can we do to mitigate the effects?
Overheating guidance and tools for building designers
A number of cool guides to help with the heat.
The UK's Modern Industrial Strategy: A 10 year plan
Previous consultation criticism, current key elements and general support with some persisting reservations.
Building Safety Regulator reforms
New roles, new staff and a new fast track service pave the way for a single construction regulator.
Architectural Technologist CPDs and Communications
CIAT CPD… and how you can do it!
Cooling centres and cool spaces
Managing extreme heat in cities by directing the public to places for heat stress relief and water sources.
Winter gardens: A brief history and warm variations
Extending the season with glass in different forms and terms.
Restoring Great Yarmouth's Winter Gardens
Transforming one of the least sustainable constructions imaginable.
Construction Skills Mission Board launch sector drive
Newly formed government and industry collaboration set strategy for recruiting an additional 100,000 construction workers a year.
New Architects Code comes into effect in September 2025
ARB Architects Code of Conduct and Practice available with ongoing consultation regarding guidance.
Welsh Skills Body (Medr) launches ambitious plan
The new skills body brings together funding and regulation of tertiary education and research for the devolved nation.
Paul Gandy FCIOB announced as next CIOB President
Former Tilbury Douglas CEO takes helm.
UK Infrastructure: A 10 Year Strategy. In brief with reactions
With the National Infrastructure and Service Transformation Authority (NISTA).
Ebenezer Howard: inventor of the garden city. Book review.
Airtightness Topic Guide BSRIA TG 27/2025
Explaining the basics of airtightness, what it is, why it's important, when it's required and how it's carried out.